Switch Mode Power Supply (120/240/480/960 W Models)
* Information in this page is a reference that you created on the basis of information in the product catalog before the end of production, may be different from the current situation, such as goods for / supported standards options / price / features of the product. Before using, please check the compatibility and safety system.
last update: February 3, 2014
Item | Nominal Input Voltage | F: 400 to 500 VAC | |||
---|---|---|---|---|---|
Nominal Input Current | 5 A | 10 A | 20 A | 40 A | |
Efficiency (400 VAC FULL LOAD) | 86% | 90% | 91% | 91% | |
Input | Voltage range | 340 to 576 V 3 AC resp. 480 to 810 VDC | |||
Frequency | 50 to 60 Hz | ||||
Current (max.)
(Vin = Range min., Pmax) |
0.5 A | 1 A | 1.5 A | 3 A | |
Power factor (400 VAC
FULL LOAD) |
0.66 | 0.66 | 0.86 | 0.86 | |
Leakage current (max.) | < 3.5 mA | < 3.5 mA | < 3.5 mA | < 3.5 mA | |
Inrush current (max.)
(Pmax) |
< 30 A @ Vin max. | < 30 A @ Vin max. | < 40 A @ Vin max. | < 30 A @ Vin max. | |
EMI filter | 2 × 10 mH | 2 × 27 mH | 2 × 6.8 mH | 2 × 2.2 mH | |
Line fuses | T2 A | T3.15 A | T4 A | T6.3 A | |
Output | Voltage adjustment range | 21.6 to 28.0 VDC min. | |||
Tolerance adjustment
accuracy |
1% | ||||
Ripple & noise (P max.) | 100 mV max. (p.p. 0-20 MHz) | ||||
Load variation influence | ±0.5% max. | ||||
Input variation influence | ±0.25% max. | ||||
Temperature variation
influence |
Less than 0.05%/°C | ||||
Startup time (max.) | 1.3 s | 1.3 s | 1.3 s | 1.3 s | |
Hold time (min.)
(Vin = 400 VAC) |
15 ms | 15 ms | 15 ms | 15 ms | |
Protection | - Short circuit protection continuative
- Over load protection - Over voltage protection |
||||
Parallel operation | Yes (for two units) | ||||
Serial operation | Yes (for two units) | ||||
Indicator | Yes (Green LED) | ||||
Others | Heat radiation | Natural air cooling | |||
Ambient temperature | -10 to 70°C (de-rating: 5%/°C for 60 to 70°C) | ||||
Temperature power
derating |
60 to 70°C see diagram | ||||
Storage temperature | -40 to 85°C | ||||
Ambient humidity | 10 to 90% noncondensing | ||||
Dielectric strength | 2.5 kVAC Input-PE (for 1 sec.; routine test)
3 kVAC Input-Output on isolation components (transformers) (for 1 sec.; high- pot routine test) 1 kVAC Output-PE (for 1 sec.; routine test). |
||||
Insulation resistance | 500 Mohm min at 500 VDC, Output - P.E. | ||||
Vibration resistance | 10 to 55 Hz, 0.375 mm single amplitude for 2 h each in X, Y and Z directions
10 to 150 Hz, 0.35 mm single amplitude for 80 min each in-X, Y and Z directions |
||||
Shock resistance | 150 m/s2, 3 times each in ±X, ±Y, ±Z directions | ||||
EMC | EN55011 (EN55022) EN61000-3-2, EN61000-4-2, EN61000-4-3, EN61000-4-4,
EN61000-4-5, EN61000-4-6, EN61000-4-8, EN61000-4-11, EN61204-3 |
||||
Approval standards
(AC and DC input) |
IEC60950-1, EN60950-1 UL60950-1, CSA 22.2 No. 60950-1, UL508 Listed *1,
EN50178, EN60204 |
||||
Life expectancy | 10 years (Vin = 400 - 500 VAC 50% of rated output current Ta = 40°C) | ||||
MTBF *2 | > 300.000hrs | ||||
Weight | 0.71 kg | 0.91 kg | 1.8 kg | 3.3 kg |
last update: February 3, 2014