CJ-series Controller Link Units
last update: July 8, 2024
Items | Specifications |
---|---|
Model | CJ1W-CLK23
3G8F7-CLK23-E *1 CJ1W-CLK21-V1 *1 3G8F7-CLK21-EV1 *1 |
Type | Wired (shielded twisted-pair cable) |
Communications method | N:N token-bus method |
Code | Manchester code |
Modulation | Baseband code |
Synchronization | Flag synchronization (conforms to HDLC frames) |
Transmission path format | Multidrop method (bus type) |
Transmission speed | The following are the maximum transmission distances depending on the transmission speed.
2 Mbits/s: 500 m 1 Mbits/s: 800 m 500 kbits/s: 1 km |
Maximum transmission
distance |
|
Maximum distance between
nodes |
Not specified. (Maximum transmission distance must be satisfied for the entire system.) |
Medium | Specified shielded twist-pair cable
Two signal wires, one shield |
Node connection method | PLC: Connection to terminal block
Computer: Connection using special (supplied) connector |
Maximum number of nodes | 32 or 62 nodes *2 *3 |
Applicable Programming
Devices |
CX-Integrator in CX-One, CX-Net in CX-Programmer *3, and Programming Console |
Communications functions | Data links and message service |
Number of data link words | Send words per node: 4,000 words max. (CJ1W-CLK[]3), 1,000 words max. (All other Units)
Number of send/receive words per node: 12,000 words max. (Pre-Ver. 1.2) 20,000 words max. (unit Ver. 1.2 or later) Total number of send words per network: 62,000 words max. |
Data link areas | PLC: Bit areas (CIO Area, Work Area, Link Area *4), Data Memory (DM), Extended DM Area (EM) Computer:
FinsGateway event memory |
Message length | 2,012 bytes max. (including the header) |
RAS functions | Polling node backup function
Self-diagnosis function (hardware checking at startup) Echoback test and broadcast test (using the FINS command) Watchdog timer Error log function |
Error control | Manchester code check
CRC check (CCITT X16 +X12 +X5 +1) |
Item | Specifications |
---|---|
Model | CJ1W-CLK23 CJ1W-CLK21-V1 * |
Applicable PLC | All CJ-series CPU Units |
Number of mountable Units | 8 max. |
Installation site | Install onto a CPU Backplane or Expansion Backplane (classified as a CPU Bus Unit). |
Storage location of network parameters and manually set data link tables |
System Bus Unit Area (in the CPU Unit parameter area). |
Storage location of routing tables | CPU Unit parameter area |
Weight | 110 g |
Current consumption: 5 V in PLC | 0.35 A |
* Discontinuation models in July 2012.
Item | Specifications | |||
---|---|---|---|---|
Model | 3G8F7-CLK23-E | 3G8F7-CLK13-E | 3G8F7-CLK53-E | |
Computer-compatible models | IBM PC/AT or compatible
CPU: Intel Celeron 400 MHz or better Main memory: 128 MB minimum One or more PCI bus slots (PCI bus revision 2.0 or later, power supply: 5 V) Free hard disk space: 70 MB min. CD-ROM drive: One required for installation Display: VGA (640 x 480 (pixels) min.) (Other conditions conform to the OS.) |
|||
Compatible OS | FinsGateway Version2003 *1
Windows 10 (32bit) Windows 8 (32bit) Windows 7 (32bit) Professional Windows 7 (32bit) Home Premium Windows Vista Business Windows Vista Home Premium FinsGateway Version3 *2 Windows XP Professional Windows XP Home Edition Windows 2000 Professional Windows NT4.0 (Service Pack 3 or higher) Windows ME Windows 98SE |
|||
Weight | 104 g | 120 g (excluding mounting bracket) | 124 g (excluding mounting bracket) | |
Current
consumption |
5 V in PLC | 0.35 A | 0.54 A | 0.60 A |
External 24 V | --- | 0.35 A | 0.35 A |
Note: Controller Link Support Boards (for PCI Bus) is no longer available to order.
Item | Specifications | ||
---|---|---|---|
Model | CS1W-RPT01 | CS1W-RPT02 | CS1W-RPT03 |
Supported Units/Boards | All wired Controller Link Units and Boards
Note: If a maximum of 62 nodes is used, models that support 62 nodes must be used. |
||
Transmission line | Wire-to-wire | Wire-to-optical (H-PCF) | Wire-to-optical (GI) |
Transmission line format | Multi-drop
Tree |
1:1 type | 1:1 type |
Installation | Repeater Units are not mounted to the PLC. They are mounted separately with screws or on a DIN Track. | ||
Weight | 130 g | 130 g (excluding mounting bracket) | 130 g (excluding mounting bracket) |
Allowable power supply
voltage range |
20.4 to 26.4 V DC (24 V DC -15 to 10%) | ||
Current consumption | 24 V DC at 0.06 A | 24 V DC at 0.07 A | |
Inrush current | 2.5 A max. at 24 V DC (5 ms after startup) |
Repeater Units are used to expand the Controller Link network for wired models. For Wired-to-optical Repeater Units, always use a set of two (1:1).
Optical Ring Controller Link Units and Boards cannot be connected to the optical cable section between Repeater Units.
last update: July 8, 2024