Page top

Industrial Automation

Industrial Automation

G7J

Power Relay

G7J

A High-capacity, High-dielectric-strength, Multi-pole Relay Used Like a Contactor

Coil Ratings

Rated voltage Rated current Coil resistance Must-operate
voltage
Must-release
voltage
Max. voltage Power
consumption
AC 24 VAC 75 mA --- 75% max. of rated
voltage
15% min. of rated
voltage
110% of rated
voltage
Approx. 1.8 to
2.6 VA
50 VAC 36 mA ---
100 to 120 VAC 18 to 21.6 mA ---
200 to 240 VDC 9 to 10.8 mA ---
DC 12 VDC 167 mA 72 Ω 10% min. of rated
voltage
Approx. 2.0 W
24 VDC 83 mA 288 Ω
48 VDC 42 mA 1,150 Ω
100 VDC 20 mA 5,000 Ω

Note: 1. The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of +15%/-20%
              for AC rated current and ±15% for DC coil resistance. (The values given for AC rated current apply at 50 Hz or
              60 Hz.)
           2. Performance characteristic data are measured at a coil temperature of 23°C.
           3. The maximum voltage is one that is applicable to the Relay coil at 23°C.

Contact Ratings

Item Resistive load (cosφ = 1) Inductive load (cosφ = 0.4) Resistive load
Contact mechanism Double break
Contact material Ag alloy
Rated load NO: 25 A at 220 VAC (1 A at 220 VAC)
NC: 8 A at 220 VAC (1 A at 220 VAC)
NO: 25 A at 30 VDC
NC: 8 A at 30 VDC
Rated carry current NO: 25 A (1 A)
NC: 8 A (1 A)
Max. switching voltage 250 VAC 125 VDC
Max. switching current NO: 25 A (1 A)
NC: 8 A (1 A)

Note: The values in parentheses indicate values for a bifurcated contact.

Characteristics

Contact resistance *2 100 mΩ max.
Operate time *3 50 ms max.
Release time *3 50 ms max.
Max. operating frequency Mechanical: 1,800 operations/hr
Electrical: 1,800 operations/hr
Insulation resistance *4 1,000 MΩ min. (at 500 VDC)
Dielectric strength 4,000 VAC, 50/60 Hz for 1 min between coil and contacts
4,000 VAC, 50/60 Hz for 1 min between contacts of different polarity
2,000 VAC, 50/60 Hz for 1 min between contacts of same polarity
Impulse withstand voltage 10,000 V between coil and contact (with 1.2 x 50 μs impulse wave)
Vibration resistance Destruction: 10 to 55 to 10 Hz, 0.75-mm single amplitude (1.5-mm double amplitude)
Malfunction:
NO: 10 to 55 to 10 Hz, 0.75-mm single amplitude (1.5-mm double amplitude)
NC: 10 to 26 to 10 Hz, 0.75-mm single amplitude (1.5-mm double amplitude)
Shock resistance Destruction: 1,000 m/s2
Malfunction: NO: 100 m/s2, NC: 20 m/s2
Endurance Mechanical: 1,000,000 operations min. (at 1,800 operations/hr)
Electrical: 100,000 operations min. (at 1,800 operations/hr) *5
Error rate *6 100 mA at 24 VDC (bifurcated contact: 24 VDC 10 mA)
Ambient temperature Operating: -25°C to 60°C (with no icing or condensation)
Ambient humidity Operating: 5% to 85%
Weight PCB terminal: approx. 140 g
Screw terminal: approx. 165 g
Quick-connect terminal:approx. 140 g

*1. The above values are all initial values.
*2. The contact resistance was measured with 1 A at 5 VDC using the voltage drop method.
*3. The operate and the release times were measured with the rated voltage imposed with any contact bounce ignored
       at an ambient temperature of 23°C.
*4. The insulation resistance was measured with a 500-VDC megger applied to the same places as those used for
       checking the dielectric strength.
*5. The electrical endurance was measured at an ambient temperature of 23°C.
*6. This value was measured at a switching frequency of 60 operations per minute.

Approved Standards

The G7J satisfies the following international standards. Approval for some international markings and symbols are still pending, however, and information on them will be added when they are approved.

UL (File No. E41643)
CSA (File No. LR35535)

Coil ratings Contact ratings Number of test operations
24 to 265 VAC
6 to 110 VDC
NO contact 25 A 277 VAC, Resistive 30,000
25 A 120 VAC, General Use
25 A 277 VAC, General Use
25 A 240 VAC, General Use 100,000
1.5 kW 120 VAC, Tungsten 6,000
1.5 hp 120 VAC 1,000
3 hp 240/265/277 VAC
3-phase 3 hp 240/265/277 VAC 30,000
3-phase 5 hp 240/265/277 VAC
20FLA/120LRA 120 VAC
17FLA/102LRA 277 VAC
TV-10 120 VAC 25,000
25 A 30 VDC, Resistive 30,000
*1 A 277 VAC, General Use 6,000
NC contact 8 A 277 VAC, Resistive 30,000
8 A 120 VAC, General Use
8 A 277 VAC, General Use
8 A 30 VDC, Resistive
*1 A 277 VAC, General Use 6,000

Note: *These ratings are bifurcated contact ratings.

Reference

UL approval: UL508 for industrial control devices
CSA approval: CSA C22.2 No. 14 for industrial control devices

VDE (File No. 5381UG)

Model Contact ratings
NO contact NC contact
G7J-4A-B(P) (T)-KM
G7J-2A2B(P) (T)-KM
G7J-3A1B-B(P) (T)-KM
25 A 240 VAC cosφ = 0.4
25 A 240 VAC cosφ = 1
25 A 30 VDC L/R ≥ 1
8 A 240 VAC cosφ = 0.4
8 A 240 VAC cosφ = 1
8 A 30 VDC L/R ≥ 1

Note: Ask your OMRON representative for details on specifications.

Reference

VDE approval: EN60255-1-00: 1997
                        EN60255-23: 1996

KEMA (File No. 2001291.02)

Model Contact ratings
NO contact
G7J-4A-B(P) (T) (Z)-KM
G7J-2A2B(P) (T)-KM
Class AC1: 25 A at 220 VAC
11.5 A at 380 to 480 VAC
Class AC3: 11.5 A at 220 VAC and 8.5 A at 380 to 480 VAC
*Class AC1: 1 A at 220 VAC
G7J-3A1B-B(P) (T) (Z)-KM

Note: Ask your OMRON representative for details on specifications.
         *This rating is the bifurcated contact rating.

Reference

KEMA approval: EN60947-4-1 for contacts