Water Leak Detector
last update: April 1, 2022
| 61F-WL-CP[]-NRA | |
|---|---|
| Supply voltage/frequency | 100 VAC - 240 VAC 50/60 Hz |
| Operating voltage range | 85% to 110% of rated voltage |
| Operating frequency range | ±5 Hz of the rated frequency |
| Power consumption | 3.2 VA max. |
| Contact ratings | 3 A at 250 VAC (Resistive load (cosφ = 1))
1 A at 250 VAC (Inductive load (cosφ = 0.4)) Minimum applicable load 5 VDC, 1 mA (reference value) |
| Ambient temperature | -10 to +55°C |
| Ambient humidity | 25 to 85% RH |
| Ambient storage temperature | -10 to +55°C |
| Ambient storage humidity | 25 to 85% RH |
| Weight | Approx. 100 g |
| Accessories | PFC-N8 |
| 61F-WL-CP[]-NRA | |
|---|---|
| Operation resistance | Variable (0 to 50 kΩ) |
| Operation resistance error | Scale 0: 0 to 10 kΩ *1
Scale 50: 50 ±10 kΩ |
| Release resistance | Operation resistance + 50 kΩ or less |
| Interelectrode voltage | 5 VAC |
| Response time | Operate: 80 ms max.
Release: 160 ms max. |
| Startup lock time | 3 s after turning on the power supply (The LED blinks during the startup lock time) |
| Insulation resistance *2 | 100 MΩ min. (at 500 VDC) |
| Dielectric strength *2 | 2000 VAC, 50/60 Hz for 1 min. |
| Life expectancy | Electrical: 100,000 operations min.
Mechanical: 5,000,000 operations min. |
| Approved standards | UL61010-1, CAN/CSA C22.2 No.61010-1
CE, RCM EN61010-1, EN61326-1 Industrial electromagnetic environment |
last update: April 1, 2022