Sockets with Push-In Plus technology
last update: May 22, 2023
Item | PYF-08-PU (-L) | PYF-14-PU (-L) | |
---|---|---|---|
Ambient operating temperature | -40 to 70°C | ||
Ambient operating humidity | 5 to 85% | ||
Rated carry current * | 10 A | 6 A | |
Dielectric
strength |
Between contact terminals of same polarity | 2,000 VAC, 1 min | 2,000 VAC, 1 min |
Between contact terminals of different polarity | 2,000 VAC, 1 min | 2,000 VAC, 1 min | |
Between coil and contact terminals | 2,000 VAC, 1 min | 2,000 VAC, 1 min | |
Insulation resistance | 1,000 MΩ min. (at 500 VDC) | ||
Weight (approx.) | 80 g | 87 g |
Item | P2RF-05-PU | P2RF-08-PU | |
---|---|---|---|
Ambient operating temperature | -40 to 70°C | ||
Ambient operating humidity | 5 to 85% | ||
Rated carry current * | 10 A | 6 A | |
Dielectric
strength |
Between contact terminals of same polarity | 1,000 VAC, 1 min | 1,000 VAC, 1 min |
Between contact terminals of different polarity | --- | 3,000 VAC, 1 min | |
Between coil and contact terminals | 4,000 VAC, 1 min | 4,000 VAC, 1 min | |
Insulation resistance | 1,000 MΩ min. (at 500 VDC) | ||
Weight (approx.) | 40 g | 45 g |
* The continuous carry current of 10 A for P2RF-05-PU is for an ambient temperature of 55°C.
At an ambient temperature of 70°C, the value is 7 A.
The continuous carry current of 6 A for P2RF-08-PU is for an ambient temperature of 55°C.
At an ambient temperature of 70°C, the value is 5 A.
Item | PTF-08-PU (-L) | PTF-14-PU-L | |
---|---|---|---|
Ambient operating temperature | -40 to 70°C | ||
Ambient operating humidity | 5 to 85% | ||
Rated carry current * | 10 A | ||
Dielectric
strength |
Between contact terminals of same polarity | 2,000 VAC, 1 min | 2,000 VAC, 1 min |
Between contact terminals of different polarity | 2,000 VAC, 1 min | 2,000 VAC, 1 min | |
Between coil and contact terminals | 2,000 VAC, 1 min | 2,000 VAC, 1 min | |
Insulation resistance | 1,000 MΩ min. (at 500 VDC) | ||
Weight (approx.) | 65 g | 100 g |
* The continuous carry current of 10 A for PTF-08-PU(-L) is for an ambient temperature of 55°C.
At an ambient temperature of 70°C, the value is 7 A.
The continuous carry current of 10 A for PTF-14-PU-L is for an ambient temperature of 40°C.
At an ambient temperature of 70°C, the value is 7 A.
Application | Applicable
sockets |
Model | Maximum
carry current |
Ambient
operating temperature |
Ambient
operating humidity |
---|---|---|---|---|---|
For Contact terminals
(common) |
PYF-08-PU(-L)
PYF-14-PU(-L) P2RF-05-PU P2RF-08-PU |
PYDN-7.75-020[] | 20 A | -40 to 70°C | 5 to 85% Rh |
PYDN-7.75-030[] | |||||
PYDN-7.75-040[] | |||||
PYDN-7.75-200[] | |||||
For Coil terminals | P2RF-05-PU
P2RF-08-PU |
PYDN-15.5-080[] | 20 A | -40 to 70°C | 5 to 85% Rh |
PYF-08-PU(-L)
PYF-14-PU(-L) |
PYDN-31.0-080[] |
Model | Ratings | Class No. | Standard No. |
---|---|---|---|
PYF-08-PU (-L)
PTF-08-PU (-L) P2RF-05-PU |
10 A 250 V | 3211 07 | CSA C22.2 No14 |
PYF-14-PU (-L) | 6A 250V * | ||
PTF-14-PU (-L) | 10 A 250 V
(Same polarity) |
||
P2RF-08-PU | 6 A 250 V |
* When power is supplied to all four poles, use with a total power current that does not exceed 20 A.
Model | Ratings | Standard No. | Category | Listed/Recognized |
---|---|---|---|---|
PYF-08-PU (-L)
PTF-08-PU (-L) P2RF-05-PU |
10 A 250 V | UL508 | SWIV2 | Recognized |
PYF-14-PU (-L) | 6 A 250 V * | |||
PTF-14-PU (-L) | 10 A 250 V
(Same polarity) |
|||
P2RF-08-PU | 6 A 250 V |
* When power is supplied to all four poles, use with a total power current that does not exceed 20 A.
Model | Ratings | Standard No. | Certification No. |
---|---|---|---|
PYF-08-PU (-L) | 10 A 250 V *1 | EN 61984 | R50327595 |
PYF-14-PU (-L) | 6 A 250 V | ||
P2RF-05-PU | 10 A 250 V *1 | R50327599 | |
P2RF-08-PU | 6 A 250 V *3 | ||
PTF-08-PU (-L) | 10 A 250 V *1 | R50440885 | |
PTF-14-PU (-L) | 10 A 250 V *2 |
*1. Ratings are for an ambient temperature of 55°C. At an ambient temperature of 70°C, the value is 7 A.
*2. Ratings are for an ambient temperature of 40°C. At an ambient temperature of 70°C, the value is 7 A.
*3. Ratings are for an ambient temperature of 55°C. At an ambient temperature of 70°C, the value is 5 A.
last update: May 22, 2023