A22LK

Guard Lock Safety Key Selector Switch

A22LK

The guard lock prevents accidental mode changes.

Certified Standards

Certification body Standards File No.
UL UL508, CSA C22.2 No.14 E76675
TÜV SÜD EN60947-5-1 (certified direct opening) Consult your OMRON representative for details.
CQC(CCC) GB/T 14048.5 Consult your OMRON representative for details.
KOSHA KS C IEC 60947-5-1 Consult your OMRON representative for details.

Note: Only models with NC contacts have a direct opening mechanism.

Certified Standard Ratings

TÜV (EN60947-5-1)

Utilization category AC-15 DC-13
Rated operating current (Ie) 3 A 0.27 A
Rated operating voltage (Ue) 240 V 250 V

Note: Use a 10 A fuse type gI or gG that conforms to IEC60269 as a short-circuit protection device. This fuse is not built
          into the Switch.

Solenoid Coil Characteristics

Type 24 VDC
Rated operating voltage (100% ED) 24 VDC ±10%
Current consumption Approx. 88mA
Insulation Class A (130°C max.)

Characteristics

Model A22LK
Allowable operating
frequency
Mechanical 30 operations/minute max.
Electrical 30 operations/minute max.
Insulation resistance 100 MΩ min. (at 500 VDC)
Dielectric strength Between terminals of same polarity 2,500 VAC, 50/60Hz for 1min.
Between each terminal and ground 6,000 VAC, 50/60Hz for 1min.
Vibration resistance *1 10 to 55 Hz, 1.5mm double amplitude (within 1 ms)
Shock resistance Destruction 1000m/s2
Malfunction *1 300m/s2
Durability Mechanical 100,000 operations min.
Electrical 100,000 operations min.
Ambient operating temperature *2 -10 to +55°C
Ambient operating humidity 35% to 85%RH
Degree of protection *3 IP65 *3
Electric shock protection class Class II
Degree of contamination 3 (EN60947-5-1)

Note: 1. Do not allow the load current to exceed the rated value.
             2. The contact ON/OFF timing is not synchronized. Confirm performance before application.
             3. Once the contacts have been used to switch a load, however, they cannot be used to switch smaller loads. The
                   contact surfaces will become rough once they have been used and contact reliability for smaller loads may be
                   reduced.
*1. Malfunction within 1 ms.
*2. With no icing or condensation.
*3. The degree of protection from the front of the panel.