Type | Cycle | Minimum scale graduation | Minimum set time | Maximum set time |
---|---|---|---|---|
Daily | 24 h | 15 min | 15 min | 23 h 45 min |
Motor Time Switch
* Information in this page is a reference that you created on the basis of information in the product catalog before the end of production, may be different from the current situation, such as goods for / supported standards options / price / features of the product. Before using, please check the compatibility and safety system.
last update: September 24, 2012
Type | Cycle | Minimum scale graduation | Minimum set time | Maximum set time |
---|---|---|---|---|
Daily | 24 h | 15 min | 15 min | 23 h 45 min |
Power supply voltage | Synchronous motor: 100/110/120 VAC, 50/60 Hz; 200/220/240 VAC, 50/60 Hz (See note 1.) Quartz motor: 100 to 240 VAC, 50/60 Hz; 12 to 24 VDC |
---|---|
Operating voltage range | 85% to 110% of rated supply voltage |
Power consumption (See note 2.) |
Synchronous motor: 3 VA max. Quartz motor: 1 VA max. at 100 to 120 VAC, 4 VA max. at 200 to 240 VAC, 1 W max. at 12 to 24 VDC |
Control output | 15 A at 250 VAC, resistive load |
Ambient operating temperature | - 10 to 55°C (with no icing) |
Ambient operating humidity | 35% to 85% |
Note:Note:
Note:Use the switch on the back of the H2F-D to change the frequency.
Note:Inrush current will briefly flow when the power supply is turned ON.
Type | Daily | ||
---|---|---|---|
Synchronous motor | Quartz motor | ||
Operating time deviation (See note 1.) Voltage influence and temperature influence |
± 3 min max. | ||
Setting error (See note 2.) |
± 3 min max. | ||
Cyclic error | ± 3 min max. | ||
Power interruption backup time | --- | 180 h min. (See note 3.) | |
Insulation resistance | 100 MΩ min. (at 500 VDC) | ||
Dielectric strength | 2,000 VAC, 50/60 Hz for 1 min (between current-carrying metal parts and non-current-carrying metal parts and between control output and operating circuit) 1,000 VAC, 50/60 Hz for 1 min (between non-continuous contacts) |
||
Vibration resistance | Destruction | 16.7 Hz with 2-mm single amplitude for 1 hour each in three directions | |
Malfunction | 10 to 55 Hz with 0.25-mm single amplitude for 10 minutes each in three directions | ||
Shock resistance | Destruction | 1,000 m/s2 5 times each in 6 directions | |
Malfunction | 200 m/s2 once each in 6 directions | ||
Life expectancy | Contacts: 10,000 operations min., Motor: 20,000 h | ||
Weight | Flush-mounting model: Approx. 150 g, Surface-mounting model: Approx. 200 g | ||
Case color | Light gray (Munsell 5Y7/1) |
Note:Note:
Note:Deviation in the ON time or OFF time.
Note:Time difference between the set time and time required to start operation when the pointer is set to the present time.
Note:Value when power has been supplied for at least 72 h at initial use.